Check the output pattern: The default NAC pattern is temporal. The strobe circuits require a continuous (Steady) output pattern. From the " Access Level 3 " menu, choose " Edit Configuration " then choose " Edit I/O ". Select " Edit Panel I/O ", then " Edit Default Pattern ". Use the up and down arrow keys to highlight the selected pattern, then press the Enter button.
Check the output pattern: The default NAC pattern is temporal. The strobe circuits require a continuous (Steady) output pattern. From the " Access Level 3 " menu, choose " Edit Configuration " then choose " Edit I/O ". Select " Edit Panel I/O ", then " Edit Default Pattern ". Use the up and down arrow keys to highlight the selected pattern, then press the Enter button. |
NFPA 72 Compliant, UL 864, Local Signaling Unit. S8255 Types: Automatic, manual, water flow and sprinkler supervisory. CSFM: 7165-0410:159 |